Human-system interfaces (HSIs) play an important role in enabling operators to communicate with the nuclear power plant (NPP) side. Getting the information required to understand a NPP’s current status or perform necessary actions for responding to a given operational context are representative operator tasks performed using HSIs. To date, HSIs have been mainly evaluated in the context of human reliability analysis (HRA). However, the current HSI evaluation that occurs during HRA may be challengeable on two fronts: (1) reflecting the unique characteristics of HSI systems and (2) considering situations in which HSIs are poorly operated due to software/hardware malfunctions. Accordingly, this study proposes an approach for specifically evaluating HSIs for digital instrumentation and controls (DI&C) systems, using Redundancy-guided Systems-theoretic Hazard Analysis (RESHA) and HRA. RESHA is a method for analyzing DI&C systems with redundancy features. In this study, we investigate how HSIs are evaluated in existing HRA methods, and what challenges exist in the current approaches. To better evaluate HSIs for DI&C systems, this study modifies the existing HSI evaluation process by additionally modeling the HSI back- and front- ends. In this paper, a HSI fault tree for the APR1400 DI&C system is introduced through a piping and instrumentation diagram. It then touches upon what aspects of the suggested method must be further researched.